http://en.wikipedia.org/wiki/Circuit_breaker
Type Instantaneous tripping current
B above 3 In up to and including 5 In
C above 5 In up to and including 10 In
D above 10 In up to and including 20 In
K above 8 In up to and including 12 In
For the protection of loads that cause frequent short duration
(approximately 400 ms to 2 s) current peaks in normal operation.
Z above 2 In up to and including 3 In for periods in the order of tens
of seconds.
For the protection of loads such as semiconductor devices or measuring
circuits using current transformers.
--